Several Common Faults And Treatment Methods Of Safety Valve

Jun 09, 2021

Leave a message

Several common faults and treatment methods of safety valve

Improper selection or use of safety valve will cause valve failure. If these faults are not eliminated in time, it will affect the efficiency and service life of the valve, and even can not play a role in safety protection. The common faults are as follows:

(1) The valve body leaks. Under the normal working pressure of the equipment, the leakage between the valve disc and the sealing surface of the valve seat exceeds the allowable level. These reasons may be as follows:

1) Dirt falls on the sealing surface. The solution office uses the lifting wrench to open and close the valve several times to wash away the dirt.

2) The sealing surface is damaged. According to the degree of damage, the method of grinding after turning is used to repair. After repair, the sealing surface shall be smooth and its roughness shall not be higher than RA = 0.2 μ m。

3) Due to improper assembly or pipe load, the concentricity of parts is damaged. Additional loads on the pipe shall be reassembled or removed.

4) The opening pressure of the valve is too close to the normal working pressure of the equipment, so that the specific pressure of the sealing surface is too low. When the valve is subject to vibration or medium pressure fluctuations, it is more prone to leakage. The opening pressure should be adjusted according to the strength of the equipment.

5) The spring is relaxed, which reduces the set pressure and causes the valve to leak. May be due to high temperature or corrosion and other reasons, should be based on the reason to replace the spring, or even replace the valve (if it is improper to choose) and other measures. If it is only caused by improper adjustment, just tighten the adjusting screw properly.

(2) Valve opening and closing is not flexible and crisp. The main reasons may be as follows

1) Improper adjustment of the adjusting ring causes the valve to open slowly or return to seat slowly. It should be readjusted.

2) The internal moving parts are jammed, which may be caused by improper assembly, dirt mixing or parts corrosion. We should find out the reason and eliminate it.

3) The resistance of the discharge pipe is too large, and a large back pressure is established during the discharge, which makes the valve not open enough. The discharge pipe resistance should be reduced.

(3) The change of account opening pressure. After the safety valve is adjusted, the actual opening pressure is allowed to have a certain deviation from the setting value. According to the provisions of gb12243-89, when the set pressure is less than or equal to 1.0MPa, the allowable deviation is ± 0.02MPa; When the set pressure is more than 1.0MPa, it is the second half of the set pressure ± 2%。 Beyond the above tolerance range is considered abnormal. The reasons for the change of opening pressure may be as follows:

1) It is caused by the change of working temperature. For example, when the valve is adjusted at room temperature for high temperature, the opening pressure is often reduced. This can be adjusted by properly tightening the screw. However, if the spring chamber temperature is too high due to type selection fading, the appropriate type of valve (such as the valve with radiator) should be replaced.

2) Spring corrosion. The spring should be replaced. When the medium is highly corrosive, the spring coated with fluoroplastics or the safety valve with bellows should be selected.

3) It is caused by the change of back pressure. When the change of back pressure is large, the back pressure stable bellows safety valve should be selected.

4) The internal moving parts are jammed. It should be checked and eliminated.

(4) The valve oscillates. That is, the valve disc is opened and closed frequently. The possible reasons are as follows

1) The discharge capacity of the valve is too large (relative to the required displacement). The rated discharge capacity of the selected valve shall be close to the required discharge capacity of the equipment as far as possible.

2) The inlet pipe diameter is too small or the resistance is too large. The inner diameter of the inlet pipe shall not be less than the inlet diameter of the valve, or the resistance of the inlet pipe shall be reduced.

3) The resistance of the discharge pipe is too large, resulting in excessive back pressure during discharge. The discharge pipe resistance should be reduced.

4) The spring stiffness is too high. The spring with smaller stiffness should be used instead.

5) Improper adjustment of the adjusting ring resulted in high re seating pressure. The position of the adjusting ring should be readjusted.