Add sealing grease method
For the regulating valve without the use of sealing grease, it can be considered to increase the sealing grease to improve the sealing performance of the stem.
Additive packing method
In order to improve the sealing performance of the packing on the regulating valve stem, the method of adding packing can be adopted. Usually double layer, multi-layer mixed packing form, simply increase the number, such as 3 pieces to 5 pieces, the effect is not obvious.
Replace graphite packing method
A large number of use of tetrafluorine filler, because of its working temperature in the range of -20 ~ +200℃, when the temperature in the upper and lower limits, big changes, the sealing will significantly decline, aging fast, short life. Flexible graphite filler can overcome these shortcomings and long service life. Therefore, some factories will all change the tetrafluoro filler to graphite filler, and even the newly repurchased regulating valve will be used after the tetrafluoro filler is changed to graphite filler. However, the return difference of graphite filler is large, and some creep phenomenon occurs at the beginning, which must be considered.