Basic error: the 20~100kPa signal is steadily increased or decreased in the input chamber (or locator), the stroke value corresponding to each point is measured, and the error of each point between the "signal-stroke" relationship and the theoretical value is calculated. The test points should be carried out at 5 points of 0%, 25%, 50%, 75% and 100% of the signal range, and the basic error of the measuring instrument should be limited to 1/4 of the basic error limit of the tested valve.
Back error: the experimental method is the same as above. In the same input signal measured on the positive and negative stroke of the maximum difference is back.
Always point deviation: experimental method as above. The basic error at the upper limit (starting point) of the signal is the starting point deviation. The fundamental error at the signal lower limit (end point) is the end point deviation.
Leakage test: Usually the test medium is room temperature water. When the pressure difference of the valve is less than 350kPa, the experimental pressure is done according to 350kPa. When the working pressure difference of the valve is greater than 350kPa, the permissible pressure difference is done according to the pressure difference. The experimental medium should enter the valve according to the specified flow direction. The outlet of the valve can be directly connected with the atmosphere or the low-pressure head measuring device connected with the outlet to the atmosphere. The leakage can be measured after confirming that the valve and the downstream connecting nozzles are fully filled with the medium. For the main valve, but also to do a strong pressure test for the valve matching the positioner, before installation, put into operation, all the technical requirements carefully clean up the accessories, such as solenoid valve, hand wheel mechanism, special tools, etc.