1. Install check valve first and then install gate valve or butterfly valve
Advantages: protects check valves, especially in parallel pumps, where the impact is borne by gate or butterfly valves when one pump does not start and the other pumps start
Disadvantages: gate valve or check valve who to protect? Once there was a case, the butterfly valve disc was broken.
2. Install gate valve or butterfly valve first and then install check valve
Advantages: can protect butterfly or gate valves, impact borne by check valves
Disadvantages: check valve who to protect, check valve is on the pressure difference to switch, if the main pipe pressure is high, the pressure of the pump is high on the open, if the use of unstable flow, then check valve will repeatedly switch, will affect the life of the check valve.