BRIEF DESCRIPTIONS
Heater Safety Valve of HFA49Y Series is a full nozzle reaction type safety valve designed for low and medium set pressure saturated steam applications. Its set pressure range is <5.0 MPa, maximal working temperature <350 DegreeC, suitable for most power plant LP steam line service.
Heater Safety Valve has the advantages of disassembly and portability, high precision, high output flow, and accurate pressure design. Its aluminum alloy body ensures high strength and pressure resistance performance.
![]() | DESIGN |
Types: Conventional safety valve | |
FEATURES | |
The solid nozzle screws into the body brings easy and convenient maintenance. |
DIMENSION AND SIZE
Type | Nominal Size,Flange,Pressure Grade, Connecting End Face | Structure Size | Weight | ||||||
HFA48Y-150Lb | NPS | DN | Flange Std | Inlet Flange | Outlet Flange | L | L1 | H | Kg |
3L4 | 80 | ASME | Class150 NPS3 RF | Class150 NPS4 RF | 165 | 155.5 | 470 | 44 | |
4M6 | 100 | Class150 NPS4 RF | Class150 NPS6 RF | 184 | 178 | 576 | 81.4 | ||
4N6 | 100 | Class150 NPS4 RF | Class150 NPS6 RF | 210 | 197 | 630 | 89.5 | ||
4P6 | 100 | Class150 NPS4 RF | Class150 NPS6 RF | 229 | 181 | 718 | 112.5 | ||
6Q8 | 150 | Class150 NPS6 RF | Class150 NPS8 RF | 241 | 240 | 810 | 157.4 | ||
6R8 | 150 | Class150 NPS6 RF | Class150 NPS8 RF | 241 | 240 | 810 | 176 | ||
8T10 | 200 | Class150 NPS8 RF | Class150 NPS10 RF | 279 | 276 | 1207 | 350 | ||
Type | Nominal Size,Flange,Pressure Grade, Connecting End Face | Structure Size | Weight | ||||||
HFA48Y-300Lb | NPS | DN | Flange Std | Inlet Flange | Outlet Flange | L | L1 | H | Kg |
3L4 | 80 | ASME | Class300 NPS3 RF | Class150 NPS4 RF | 165 | 155.5 | 552 | 64.5 | |
4M6 | 100 | Class300 NPS4 RF | Class150 NPS6 RF | 184 | 178 | 576 | 87 | ||
4N6 | 100 | Class300 NPS4 RF | Class150 NPS6 RF | 210 | 197 | 630 | 96.5 | ||
4P6 | 100 | Class300 NPS4 RF | Class150 NPS6 RF | 254 | 206 | 790 | 122.5 | ||
6Q8 | 150 | Class300 NPS6 RF | Class150 NPS8 RF | 241 | 240 | 810 | 161.1 | ||
6R8 | 150 | Class300 NPS6 RF | Class150 NPS8 RF | 241 | 240 | 1080 | 286 | ||
8T10 | 200 | Class300 NPS8 RF | Class150 NPS10 RF | 279 | 276 | 1207 | 388 | ||
DEFINITIONS AND TERMINOLOGY |
● ACCUMULATION Pressure increased over the maximum allowable working pressure of the vessel during discharge through the pressure-relief valve (expressed as a percent of that pressure) is called accumulation. |
● DESIGN PRESSURE The pressure used or designated in the design of equipment for the purpose of determining the minimum permissible thickness of the pressure parts at a designated temperature, exclusive of any thickness allowances added for corrosion and for loadings other than pressure. |
● BLOW DOWN Difference between set pressure and reseating pressure of a safety valve are expressed in percent of the set pressure or in bar or kPa. |
● MAXIMUM ALLOWABLE WORKING PRESSURE The maximum gauge pressure permissible at the top of a completed vessel in its operating position for designated temperature. The vessel may not be operated above this pressure or its equivalent at any metal temperature other than that used in its design. Consequently, for that metal temperature, it is the highest pressure at which the primary pressure-relief valve is set to open. |
● OVERPRESSURE Pressure increase over the set pressure of the relieving device is overpressure. It is the same as accumulation when the relieving device is set at the maximum allowable working pressure of the vessel and may be greater than the allowable accumulation if the valve is set lower than the vessel MAWP. |
● LIFT The actual travel of the disc from the closed position when a valve is relieving. |
● SET PRESSURE Inlet pressure to which a safety valve is adjusted, in a test stand or other source of pressure, to open with an atmospheric discharge or atmospheric back pressure. |
● RESEATING PRESSURE The values of inlet static pressure at which the disc re-establishes contact with the seat or at which lift becomes zero. |
● BACK PRESSURE Pressure on the discharge side of safety-relief valves is back pressure. |
● BUILT-UP BACK PRESSURE Built-up back pressure is the pressure in the discharge header which develops as a result of flow after that the safety-relief valve opens. |
● SIPERIMPOSED BACK PRESSURE Superimposed back pressure is the pressure in the discharge header before the safety-relief valve opens. |
Hot Tags: heater safety valve, China, suppliers, manufacturers, factory, custom, price, cheap, for sale, valve affiliate marketing safety valve, valve referral marketing safety valve